Delete, hide, and replace plants

Delete plants

The plant is deleted, including the entire data point history and all personal settings. A controller displays in the tab "Unassigned"↑ as a new plant if the controller registers in the cloud. The user can no longer access the plant. Only the tenant administration can reassign↑ or reactivate them using an activation key. In contrast to "Hide" plant, settings specific to the plant are also deleted.

Hide plants

In contrast to deleting a plant, the specific plant settings are retained under hide plant and are immediately available on the plant is reassigned.

Replace plants

"Replace Plant" typically applies to a defective controller. The workflow is the same as depicted below.

info

Historical data remains (due to Cloud storage), with the exception of the offline time.

On the plant

  1. The new controller is prepared with the same hardware and loaded application set.
  1. Uninstall the defective controller and disconnect from Ethernet.
  2. Label the defective controller and NEVER reconnect it to the Ethernet.
  3. Using the SCOPE tool, enter the distributor information on the new controller and enable the connection with EnableConnection (see "Connect to cloud (CSL)").
  4. Read the ActivationKey via the SCOPE browser in "SystemObjects > CSL-Config" and provide it to your tenant administrator.
  5. Connect the new controller to the Internet.

In Climatix IC

  1. You have the portal role of tenant administrator.
  1. Check under "Administration > Plant > Unassigned" to ensure that the new plant has completed the reading of the data points.
  2. Select the defective controller in the "Assigned" tab and go to plant settings via secondary navigation.
  3. Click "Replace Plant".
  4. Enter the key for the replacement controller under "New activation key".
  5. Confirm with OK to replace the controller.
  6. Wait about 1...5 minutes.
  7. "Plant settings" displays with all the data from the replaced controller.
  8. Confirm takeover of the data with "Save".
  1. The new controller controls the plant the same as for the exchanged device.